According to Category B of the local fire safety regulations, fire detection equipment in all premises is including the following:
- Smoke photo-electronic fire sensors
- Manual fire indicators with built-in modules installed in emergency exits and escape routes.
Fire alarm system is equipped with an analogous fire alarm system coordinated from the main panel and includes: smoke and heat detectors, manual fire alarms with safe glass and fire detectors behind suspended ceilings.
- Automatic set up of the fire alarm and fire alert
- Automatic sprinkler and water drencher systems
- Automatic set up of a gas fire fighting module in the premises, where a diesel generator is located
When the fire alarm is activated:
- The supply-and-exhaust ventilation system automatically switches off
- The smoke removal system for the floor corridors and underground parking automatically switches on
- The air supply system for staircases and elevator shafts automatically switches on
- The voice and light warning system (flashing light strobes located by the loudspeakers near building entrances) automatically switches on
- The elevators are lowered to the 1st floor, switch off and the elevator doors are opened
- The fire alert is passed by radio channel to the main panel of fire department
- Automatic water sprinkler system installed in each room
- Nine manual fire nozzles connected to fire cocks by force-fire hoses on each floor
- Three dry powder extinguishers in each fire cabin to localize fires
- Built-in fire tank with 20 m3 of water reserve
- Built-in pumping station for automatic fire fighting with an output of 141.1 m3/hour